SDB系列空调管道直燃燃烧器使用说明书。
-11-APPENDIX A Calculation Method &Examples
SUNSRAYS normally uses the following formula to calculate the required net heat input:
Q (kW)=Airflow (Nm3/s)x Temperature rise (ºC)x Air Density x Specific Heat of Air
or
Q (Btu/h)=Airflow (scfh)x Temperature rise (ºF)x Air Density x Specific Heat of Air
The required gross gas input =Required net heat input/0.92
The gross gas input ÷firing rate per 12”(305mm)section will determine the required burner length.Minimum section length =6”(150mm).
Example:
A.Airflow =5Nm3/s
B.“Air on”temperature =-5ºC
C.“Air off”temperature
=25ºC D.Preferred firing rate =600,000Btu /176kW)per 12”(305mm)section
Required net heat input =181kW
Required gross gas input =197kW
Number of 6”(152.5mm)sections =197÷176=1.12x 2=2.24which is “rounded up”to 3.
Total burner length =3x 6”=18”(or 3x
152.5mm =458mm)The required net profile area (excluding the burner)=Airflow/Profile velocity (determined by burner firing rate)Net Profile Area (excluding burner)=5Nm3/s/14.7m/s =0.34m2
Total Profile Area (including burner)=Net Profile Area +Burner Profile Area (0.03m2/6”burner section)=0.34+0.09=0.43m2
Required width of the profile opening =Total burner length +100mm (4”)=558mm (rounded to 560mm)Required height of the profile opening =Total Profile Area/Required Width of Profile Opening
=0.43x 106/558=770mm
Minimum duct width =Burner length +305mm (152.5mm
at either side)=763mm (rounded to 770mm)Minimum duct height =Height of profile opening +200mm (8”)=970mm