ACS800-RDCU-硬件手册-英文(9)
发布时间:2021-06-07
发布时间:2021-06-07
ACS800
9
Analogue outputs (X21)
General: Two programmable current outputs: 0 (4) … 20 mA, RLResolution: 0.1% (10 bit)
Inaccuracy: ±1% (Full scale range) at 25 °C (77 °F). Temperature coefficient: ±200 ppm/°C (±111 ppm/°F) max.
Digital inputs (X22)
General: Six programmable digital inputs (common ground: 24 VDC,
-15% … +20%) and a start interlock input (DIIL). Group isolated, can be divided into two isolated groups (see Isolation and grounding below).Thermistor input: 5 mA, < 1.5 kohm “1” (normal temperature), > 4 kohm “0” (high temperature), open circuit “0” (high temperature).
Internal supply for digital inputs (+24 VDC) is short-circuit proof. An external 24 VDC supply can be used instead of the internal supply.
Isolation test voltage: 500 VAC, 1 min
Logical thresholds: < 8 VDC “0”, > 12 VDC “1”
Input current: DI1 to DI5: 10 mA; DI6: 5 mA
Filtering time constant: 1 ms
24 VDC power output (X23)
Voltage: 24 VDC ±10%, short-circuit proof
Maximum output current: 250 mA (without any optional modules inserted)Relay outputs (X25, X26, X27)
General: Three programmable relay outputs
Switching capacity: 8 A at 24 VDC or 250 VAC; 0.4 A at 120 VDC
Minimum continuous current: 5 mA rms at 24 VDC
Maximum continuous current: 2 A rms
Isolation test voltage: 4 kVAC, 1 min
Slot 1 (X31)
General: For connection of I/O extension modules (such as RAIO and RDIO), pulse encoder interface (RTAC), or fieldbus adapters (such as RPBA and RMBA)Slot 2 (X32)
General: For connection of I/O extension modules (such as RAIO and RDIO) or pulse encoder interface (RTAC)
DDCS (X33)
General: For connection of RDCO-0x(C) DDCS Communication module
RDCU-02(C) Control Unit Hardware Manual