TechTopics No. 09We are often asked to provide estimated heat generation data for our equipment. This issue of TechTopics provides information that allows calculation of approximate heat generated by the type GM38 switchgear under assumed loading conditions. The heat generation data given in the table is based on full-rated continuous current. Actual heat generation calculations must take into account the true loading of the equipment. The amount of heat generated is related to the square of the current, so a circuit breaker operating at one-half rated current will have heat generation only one-quarter of that at full-rated continuous current. Because the effect of the square relationship is very significant, it is overly conservative to estimate heat generation based on the assumption that all sections and all circuit breakers each carry their rated continuous current at all times. Air conditioning systems sized based upon such estimates will be much larger than the real operating conditions will require.
Table 1: Approximate full load heat generation (in watts (W)) for type GM38 switchgear (up to 38 kV)
Continuous current - circuit breaker (rows 1-3) or main bus (row 4) Rated current Category Actual current Circuit breaker cell with circuit breaker Vertical section with main bus Space heaters per vertical section Voltage transformer (VT) stationary Control power transformer (CPT) (stationary) Relaying and instrumentation per circuit breaker cell Microprocessor type Electromechanical non-complex Electromechanical complex1,200 A 461 W 211 W 1,000 W 250 W 4% of CPT kVA rating 50 W 100 W 200 W to 300 W 2,000 A 738 W 275 W 1,000 W 250 W 4% of CPT kVA rating 50 W 100 W 200 W to 300 W 3,000 A 1,443 W 452 W 1,000 W 250 W 4% of CPT kVA rating 50 W 100 W 200 W to 300 W 1,200 A 2,000 A 3,000 A
Heat generation estimation for type GM38 switchgear (up to 38 kV)
Answers for energy.
Notes on assumptions:
Space heaters, when provided, are not 1.
normally controlled by a thermostat. Hence, their load is represented as a continuous load. The purpose of space heaters is to prevent condensation, and this is not limited by the absolute temperature. Even when a thermostat is used to control the heaters, it is set to shut the heaters off at a
temperature of approximately 110º F.Therefore, in an air-conditioned room, the heaters would be energized continuously.Heat generated by current 2.
transformers is ignored as it is usually insignificant and varies according to the CT ratio as well as the loading.The CPT heat generation estimate is 3.
very conservative and assumes the CPT is operated at full-rated capacity. If normal loading is at less than full rating, heat generation may be
adjusted by the square of the percent loading.Relaying and instrumentation heat 4.
generation estimates are very approximate and are normally
estimated on the basis of the number of circuit breaker cells. Extensive relaying and instrumentation may
warrant additional conservatism in the estimation of associated heat generation.Conversion factor: watts x 3.415179 = 5.
BTU/hour.
Table 2: Calculations
To estimate the heat generated under actual loading conditions, determine the component heat generation for each of the components indicated in Table 1. Estimated heat generation for circuit breakers should be adjusted for actual loading based on the ratio of the squares of the actual current and the rated current.
To be precise, this adjustment should also be made for the actual current loading of the main bus for each individual vertical section, but this is frequently ignored in the interest of simplification. Instead, the main circuit breaker loading is usually assumed to be equal to the main bus loading in all vertical sections.
Example: Assume a lineup with five vertical sections, one 2,000 A main
circuit breaker (loaded to 1,650 A), three 1,200 A feeder circuit breakers (loading 850 A, 200 A and 600 A), 2,000 A main bus and space heaters. The lineup
includes one set of VTs, one 15 kVA CPT and microprocessor relaying, and
instrumentation. The calculations would be as described in Table 2.
If true loading were not considered (for example, all calculations performed on the basis of full-rated current), the calculations would yield a heat generation of 9,546 W.
For more information, please contact your local Siemens representative.
Published by and copyright © 2009:Siemens AGEnergy Sector
Freyeslebenstrasse 1
91058 Erlangen, Germany
Siemens Energy, Inc. 7000 Siemens Road
Wendell, North Carolina 27591 USA
For more information, contact +1 (800) 347-6659
http:///energy
Siemens Energy, Inc.
Order No. E50001-E710-A162-X-4A00
All rights reserved.
Trademarks mentioned in this document are the property of Siemens AG, its affiliates or their respective owners.
Subject to change without prior notice. The information in this document contains general descriptions of the technical options available, which may not apply in all cases.
The required technical options should therefore
be specified in the contract.
http:///energy